Answers

Jun 15, 2023 - 01:02 AM
BitCool BC-888, like all fluids with high surface tension, will "wick" or move inside a cable sheath. We recommend two ways to resolve this: You can cut the outer plastic sheath just enough to allow air to enter, which destroys the capillary effect, or you can place a plug of silicone sealant inside the cable to prevent internal movement of fluid. Please search our FAQ for "wicking" or "Capillary", as we have detailed instructions on how this is done.